San Diego County
No ban. Offsets apply once the site's NOx potential reaches 25 tons a year (federal major source in a Severe ozone area), at 1.3 to 1: about 12 MW of gas 24/7 on an otherwise clean site (our estimate).
Only with a months-long air permit. Together with California.
Permitted plant: Possible (Offsets from 25 tons NOx/yr site-wide)Rentals under 12 months, no air permit: No
Rule 20.3(d)(5) requires offsets for an emissions increase that constitutes a new major stationary source, new federal major stationary source, or major modification for NOx or VOC. Rule 20.1 Table 20.1-5b sets the federal major source NOx level at 25 tpy for a Severe ozone area (50 tpy state major in Table 20.1-6b). Table 20.3-2 sets a 1.3 to 1 offset ratio for Severe.
Permitted gas generation
A new prime gas engine needs a district permit with BACT; offsets apply only once the site's NOx potential reaches 25 tons a year (about 12 MW of gas running 24/7 on an otherwise clean site, our estimate).
Rentals kept under 12 months
California's portable registration can't supply a site's primary power, so rented units need a district permit like any prime engine. Source
Details
- Who it covers
- new and existing
- Where
- San Diego County
- Status
- In force
- Effective
- October 28, 2022
- Authority
- San Diego County Air Pollution Control District (SDAPCD)
- Last checked
- November 8, 2026
Sources
- SDAPCD Rule 20.3 (rev. adopted 10/14/21, effective 10/28/22), (d)(5) primary
shall not issue an Authority to Construct ... for any new or modified stationary source ... which results in an emissions increase that constitutes a new major stationary source, a new federal major source, a major modification, or a federal major modification for NOx or VOC ... unless emission offsets are provided
- SDAPCD Rule 20.1 (rev. adopted 10/14/21, effective 10/28/22), Table 20.1-5b primary
Oxides of Nitrogen (NOx)* marginal or moderate 100 serious 50 severe 25 extreme 10
For information only, not legal advice. Confirm with your air agency and fire marshal before you rely on it. Spot an error? Email tyler@relayenergy.us.