Port Wentworth, GA
Zoning bars generators as primary power at data centers except in emergencies.
Likely no gas route.
Permitted plant: No (Zoning ban)Rentals under 12 months, no air permit: Likely no
Port Wentworth added data centers to its zoning code on Dec 18, 2025 (Ord. 2025-12-01). Data centers are permitted in the I-1 district under Sec. 7.270, which says: "Except for emergency situations, testing, or compliance purposes, external generators or power supply shall not be used for primary power." Emergency situations "shall include, but not be limited to, a power outage." The city also caps the number of data centers at one per 27,500 residents. The ordinance does not say how it treats existing sites.
Permitted gas generation
External generators can't be used for primary power except in emergencies, testing or compliance. 'Emergency situations' is open-ended ('include, but not be limited to, a power outage'), so a grid wait is not plainly excluded; we read a months-long bridge as primary power, which the text bars.
Rentals kept under 12 months
'External generators or power supply' covers trailer units (our reading). The open-ended emergency definition leaves some room. Source
Details
- Who it covers
- data centers under Sec. 7.270 (permitted in I-1); existing sites not addressed
- Where
- City of Port Wentworth only
- Status
- In force
- Effective
- December 18, 2025
- Authority
- City of Port Wentworth, GA (Mayor and Council, Dec 18, 2025)
- Last checked
- November 8, 2026